Diffusion absorption refigeration
Paulina Young
Created on April 20, 2023
More creations to inspire you
LET’S GO TO LONDON!
Personalized
SLYCE DECK
Personalized
ENERGY KEY ACHIEVEMENTS
Personalized
CULTURAL HERITAGE AND ART KEY ACHIEVEMENTS
Personalized
ABOUT THE EEA GRANTS AND NORWAY
Personalized
DOWNFALLL OF ARAB RULE IN AL-ANDALUS
Personalized
HUMAN AND SOCIAL DEVELOPMENT KEY
Personalized
Transcript
Start
The ammonia/water solution flows to the generator where it is heated to 180 °C and some ammonia evaporates.
Next
The vapor forms bubbles that push columns of liquid solution in the pump-tube up to the liquid–vapor separator.
Next
Ammonia vapor is separated out from the solution in the separator and then is purified at the rectifier, and then is liquefied in the air-cooled condenser.
Next
The weak solution is collected at the separator and returns to the absorber via a solution heat exchanger.
Next
The ammonia liquid passes to the evaporator, which is divided into two sections: a freezer and a food chiller.
Next
Because the evaporator is charged with hydrogen, and the density of ammonia is considerably greater than that of hydrogen, so the vapor mixture (ammonia and hydrogen) becomes heavier as ammonia continues to evaporate, so it drops from the freezer to the food chiller and enters the absorber.
Next
In the absorber, ammonia is absorbed into the solution, the vapor becomes lighter, because there is less ammonia but more hydrogen, and thus it rises to the top. This causes a circulation of hydrogen in the evaporator and absorber.
Next
Again, because ammonia is heavier than hydrogen, at the higher part of evaporator, in the freezer, less ammonia, more hydrogen, so the partial pressure of ammonia is lower, then the evaporation temperature is lower, between −30 and -18 °C.
Next
More ammonia at the lower part of the evaporator, at the food chiller, so its partial pressure is higher at this part, and the corresponding evaporating temperature is higher, around -5 °C.
summary
So, you see, the auxiliary gas, hydrogen, or helium, is used as a capping gas, creating low partial pressure of ammonia in the evaporator, providing pressure equalisation for ammonia between the condenser and evaporator.
Read more
Its application is limited to small refrigerators only, with low refrigeration capacity, up to 200 W, because of the limited flow rate of bubble pump. Its efficiency is relatively poor, COP of around 0.2