The BC Box must be installed Indoors and kept within normal room conditions and temperatures. The BC Box must not be exposed to moist conditions due to the electrical components within the BC Box. . As the refrigerant noise from the BC Box can cause disturbance in areas with very little background noise, the box should be installed in an unoccupied area (recomended 5m away from an Indoor fan coil). The diagrams to the left and below show reccomended distances around the BC box for access and Serviceing purposes.
200mm
100mm
Positioning BC Box
The Drain pan can be removed from the bottom of the BC Box for maintenance purposes.
The BC Box requires a condensate drain fitting to the drain outlet point. The brackets (as shown on the right) on the corners of the BC Box require adjusting so the condensate water will run to the side of the box with the drain outlet. The drain must flow on gravitational fall after this point.
Drain Pan Bracket
Drain connection
BC Box Condensate Removal